M-Bus level converters

With the M-Bus level converters from the MPW or MPW-IP series from STV Electronic, you can easily, safely and powerfully connect your controller, such as the Smart Manager 4.0 for energy data acquisition and control, to your M-Bus network,

Our level converters connect the meter data of your sensors and also the control of your actuators in the M-Bus network via the Ethernet interface and optionally via an additional serial interface (RS-232 or RS-485).

The parameters are set on the integrated website. If desired, this can be password-protected against unauthorized changes.

What is special about our level converters?

The devices have a narrow width. With a width of only 1DU, the MPW2 offers you the option of integrating up to two standard loads (1.5 mA each) into your control system. The MPW6 creates a maximum of 6 standard loads with a width of only 2TE, the MPW16 only requires a width of 3TE for 16 standard loads. All larger devices up to 128 standard loads are only 4HP wide.

All devices are characterized by simple commissioning. Devices with a serial interface (RS-232, RS-485 or USB) do not require any parameterization. The devices with an IP interface support IPv4 and IPv6 as well as MQTT and have a simple parameterization interface with additional diagnostic functions. They can also be parameterized remotely. You can find more information on this in the operating instructions in our downloads.

The high M-Bus voltage of 37-40 V enables large M-Bus networks to be operated safely. The intelligent controller takes over the management itself.
With M-Bus transmission rates from 300 to 38400 baud, the level converters are also suitable for fast M-Bus devices.

So you have the full control about your energy management and your resource consumption at all times and operate your production plants and buildings efficiently, even remotely.

Level converter of the MPW series

M-Bus Pegelwandler Serie MPW

  • Protocols:
    MQTT, IPv4, IPv6
  • Available interfaces:
    1 x RS-232 oder: 1 x RS-485 oder 1 x USB
  • Power supply:
    24 V DC ± 20 %
    24 V AC ± 5 %
  • M-Bus-voltage: 
    37 V
  • M-Bus current: 
    für max. 2, 6, 8, 16, 32, 64 oder 128 standard loads á 1,5 mA
  • Galvanic isolation
  • Collision detection
  • M-Bus-transmission-rate:
    300 … 38400 Baud
  • Montage:
    Carrier rail 35
    or with Screws

Level converter of the MPW-IP-series

M-Bus level converter MPW-IP

  • Protocols:
    MQTT, IPv4, IPv6
  • Available interfaces:
    1 x Ethernet oder 1x Ethernet + 1 x RS-232 oder: 1 x Ethernet + 1 x RS-485 
  • Power Supply:
    24 V DC ± 20 %
    24 V AC ± 5 %
  • M-Bus-voltage: 
    37 V
  • M-Bus current: 
    für max. 2, 6, 8, 16, 32, 64 oder 128 Standardlasten á 1,5 mA
  • Galvanic isolation
  • Collision detection
  • M-Bus-transmission-rate:
    300 … 38400 Baud
  • Montage:
    Carrier rail 35
    oder with screws

Individual service and advice

We will find the right solution for your requirement. Our experts support you in the development of your individual solution, in robot programming, software and hardware development as well as programming your PLC.

If you have any questions or need advice, please contact us!